2. Commissioning
2-39
Festo Festo P .BE CP FB13-E-EN en 9910c
Octet Designation Explanation
2and3 WD_Fact_1
WD_Fact_2
Range 1-255: The response monitoring time of the
CP system is transferred wit h t hese two octets:
TWD [s] = 10ms x WD_Fact_1 x WD_Fact_2
4 Minimum station delay re-
sponder (min T
SDR
)
The minimum time the CP system must wait, before
the reply telegram may be sent t o the DP master.
5and6 Ident_Number Transfer the Ident. number (= F13C) of the CP sys-
tem; Parametrizing telegrams to the CP system are
only accepted if the transferred and the pro-
grammed Ident. numbers are the same.
7 Group_Ident Not supported by the CP system
8...3 2 User_Prm_Data Not supported by the CP system
2.3.3 Send configuration data
The configuration data are transferred from the DP master to
the CP system with the function Chk_Cfg.
Please note
The configuration of a CP system must be carried out as
follows:
– per string: a DP identifier for inputs and outputs.
– via sum identifier: sum of the input bytes and sum of the
output bytes.