Configuration (= equipment on valve terminal)
Enter:
for each group of 8 inputs: 8DI
for each group of 8 outputs: 8DO
The entry fields must be assigned in
ascending order without gaps; no field may
be unused. Always enter inputs before out-
puts.
Example 1:
Valve terminal with 3 x 8-input modules,
+ 12 single solenoid valves.
Configuration:
8DI, 8DI, 8DI, 8DI, 8DO, 8DO
The 4 status bits increase the number of
inputs to 32 in this case (24I + 4I unused
+ 4 status bits).
Example 2:
Valve terminal with 10 single solenoid
valves and 6 double solenoid valves.
Configuration:
8DO, 8DO, 8DO