5.5 DIAGNOSIS VIA PROFIBUS-DP (DP-SIEMENS)
General
Diagnostic words
The diagnostic information of a valve terminal is
grouped together in diagnostic words.
With these diagnostic words, the following error
states are communicated to the controller.
• operating voltage of the valves/outputs
< 21.6 V (V
val
)
• operating voltage of the valves/outputs
< 10 V (V
out
)
• operating voltage of the sensors
< 10 V (V
sen
)
• output overloaded/short circuited
• AS-i error (bus, power and slave error)
• error in analogue processing.