EasyManua.ls Logo

Fluke Endurance E3ML - Outputs; Analog Output (current loop); Relay Outputs

Fluke Endurance E3ML
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Endurance® Series
Users Manual
44
Figure 34: Deadband Example
7.8. Outputs
7.8.1. Analog Output (current loop)
Is a current loop output circuit to drive analog output lines. It can be set to 0-20mA or 4-20mA
output current range. Direct connection to a recording device (e.g., chart recorder), PLC, or
controller is possible. The total analog output circuit impedance is limited to 500Ω. A 16-Bit
DAC (Digital Analog Converter) guarantees a current loop resolution better than 0.1 per
temperature unit (°C / °F) over the total measurement range. A specific feature for the testing
or calibrating of connected equipment allows the current loop output to bet set to specific values,
under range or over range in RS485 or LAN/Ethernet operation mode. Via such functionality
you can force the circuit, operating in the 4-20mA mode, to transmit an output current less than
4mA (e.g. 2.0 or 3.0mA) or above 20mA (e.g. 21.0 or 22.0mA).
7.8.2. Relay Outputs
The relay output is used as an alarm for failsafe conditions or as a setpoint relay. Please refer
to section 11.2 Fail-Safe Operation on page 89. Relay output relate to the current target
temperature, displayed on the green 7-segment LED display. The relay output can be used to
indicate an alarm state or to control external actions. The relay functionality can either be set
by the control panel (user interface), an RS485 or LAN/Ethernet command in dependence of
the connected equipment to the following states:
NO (NORMALLY OPEN)
NC (NORMALLY CLOSE)
PO (PERMANENTLY OPEN)
PC (PERMANENTLY CLOSE)
The relay states PO / PC can be used to detect wiring problems between the Endurance sensor
and the process environment, where the relay contact signal acts as a trigger.
7.8.3. Trigger
AVERAGE, PEAK HOLD or VALLEY HOLD can be reset by shorting the Trigger input signal to
Ground for a minimum of 10 msec. This can be done either with a momentary switch or a relay.
The Reset signal causes a new reading of the current measured temperature and restarts the
selected signal post processing function.
962°C
958°C
Setpoint: 960°C
Relay Changes State
Time
Normal State
Alarm
Alarm
Normal State
Deadband
Object Temperature
w ww. . com
information@itm.com1.800.561.8187

Table of Contents

Related product manuals