Options
PROFINET IO (Communication Option 1)
53
8.7.3. Parameter Setting
The parameter setting of a connected pyrometer happens via “record data” sets. The I/O
module allows diagnostics message to be locked or released. Once all parameter settings are
performed, the I/O device signals that it is ready to send cyclic productive data.
8.7.3.1. Pyrometer parameters
Certain pyrometer characteristics are parameterizable during the configuration. The parameters
of the pyrometer substitute are used to set the overall settings of the PROFINET I/O node.
Some of the setting are used in the module as default settings and can be optionally overwritten
within the module configuration.
Relay alarm output control
normally open,
normally closed,
permanently open,
permanently closed.
off / on / flashing/ trigger
Bottom temperature of output
Set bottom temperature of
analog output
Top temperature of output
Set top temperature of analog
output
8.7.3.2. Profinet alarm behavior
Message diagnostics alarm
The diagnostics information of
pyrometer is not transferred to
the PROFINET IO controller
is transferred to the PROFINET
IO controller
The process alarm of pyrometer
is not transferred to the
PROFINET IO controller
is transferred to the PROFINET
IO controller
set process data to zero,
set process data to last value
8.7.4. Structure of the input/output data
8.7.4.1. Pyrometer module input data
The input data length is 23 Byte.