Figure 40: Device Settings (EDS)
Manual configuration of the Ethernet/IP pyrometer is based on a Generic Ethernet module. In
this case, the assembly instance number and size must be typed in. The device settings are:
Data type: SINT
Input assembly instance 101, size 23 byte
Output assembly instance 100, size 5 byte
Configuration assembly instance 102, size 0 (the size of the configuration assembly is
58 bytes, however, sending it empty will cause an I/O failure. Configuration assembly
is available when using EDS file.)
Figure 41: Selecting Generic Ethernet Module from the Library