Options
Ethernet/IP (Communication Option 2)
59
Figure 42: Device Settings via Manual Configuration
8.8.3. Parameter Setting
All settable parameters of an Endurance pyrometer are available in the Configuration Data.
Changing the parameters this way can only happen upon device initialization, i.e. when
downloading the program to the PLC (default values are sent if no changes have been made).
Once the parameter setting has been performed, the I/O device is ready to send cyclic
productive data. While certain pyrometer characteristics are parameterizable only during the
configuration, others can also be set in the data exchange mode using Output Data. The tables
below contain all the parametrizable characteristics and are followed by a short implementation
description.
8.8.3.1. Pyrometer Parameters, per Configuration Data
The parameters included in the Configuration Data are accessible through Controller Tags in
the Rockwell PLC programming environment. Changing them in the controller tags will first
have effect after downloading the program to the PLC. The Rockwell programming software
allows however for an easy saving of these tags so that the values can always be sent as
default upon initialization.
The configuration data length is 58 Byte.