106 Faults and warnings
9.3.2.3 Waiting
The following faults prevent the hand terminal from initializing:
The CAN bus address of the terminal is not the same as the one defined in setup of the of
the automatic feeder.
The feeder control unit is not active.
The message terminal Vxx.xx waiting appears.
You can correct the fault as follows:
1. Start search mode: Press when you switch on the feeder and keep this key de-
pressed.
2. When the display reappears, you must check that the feeder controller is working.
9.3.2.4 Searching
When the hand terminal is in search mode, the message terminal Vxx.xx searching will ap-
pear.
You can correct the fault as follows:
Check that the feeder is working.
If the message is not automatically hidden in about 10 seconds, you must check the feeder
control.
9.3.3 Boot loader
9.3.3.1 Waiting for update
The following faults trigger the message boot loader Vxx.xx waiting for update:
The automatic feeder’s control program is not able to run.
Update the program using an SD card or the FTP Manager.
The boot loader was (accidentally) activated while switching on.
If when the automatic feeder was being started the was accidentally depressed
9.3.3.2 Flash programming
The message boot loader Vxx.xx flash programming will appear whilst the program is being
updated.
Wait until the update has been completed.
9.3.3.3 Starting program
The message boot loader Vxx.xx starting program will appear when the boot loader for the
automatic feeder starts.
Wait until the program has started.