TFC100 Rev180215
19
Error Codes and Fault Warnings
Refer to Calibration, Maintenance, and Troubleshooting Section for detailed information.
Note: The TFC100 does not have a message display. Information is only shown in the 4-digit display.
Table 5. Error Codes
Code TFC200/300/400
Message Display
Description
E01 PUMP NOT
DETECTED
Pump communications failed
E02 MOTOR
OVERLOAD
Over current condition sensed
E03 MOTOR DRIVER
HI TEMP
Over temperature sensed
E04 MOTOR DRIVER
SHUTDOWN
Over temperature shutdown; control module to off mode
E05 TEMP SEN
FAILED
No temperature sensor signal
E06 RPM SEN
OPEN
RPM sensor failure, circuit open
E07 RPM SEN
SHORTED
RPM sensor failure, circuit shorted
E08 MOTOR
FAILED
Motor not turning; control module to off mode
E09 DRIVER
LIMIT
Hardware power limit, over current protection
E10 POWER
LIMITED
Motor does not come up to requested speed, RPM low
E11 NO RPM
DETECTED
No RPM detected from the pump motor
E12 NO ABF
DETECTED
Auto ush communications failed; no auto ush mode
E13 FOAM A
VALVE
Foam A valve failed to open
E14 FOAM B
VALVE
Foam B valve failed to open
E15 FLUSH
VALVE
Flush valve failed to open
E16 FOAM A
VALVE
Foam A valve failed to close
E17 FOAM B
VALVE
Foam B valve failed to close
E18 FLUSH
VALVE
Flush valve failed to close
E19 FOAM A+B
VALVES
Auto Flush Valves A+B
Failed to Open
E20 NO MOTOR
POWER
Main Motor Power Lost
L01 MANUAL
MODE
Logs manual mode operation
L02 SVC OIL
FOAMPUMP
Change pump oil at rst 50 hours than every 500 hours; use code P122 to
clear service oil message
L03 FLUSH
SYSTEM
After B foam operation shows as a reminder to ush