TFC100 Rev180215
16
OPERATION
The TurboFoam system automatically injects foam concentrate into the water ow to provide a consistent
foam solution at the discharge regardless of water ow uctuations.
When power is supplied to the system, the control module FLOW display shows OFF, the message display
shows the date and time or total ow rate for all sensors when a summing box is installed.
When the ON/OFF button is pressed the LED comes on and the control module is active in the auto mode.
The FLOW display shows the water discharge ow rate
The % display shows the last used value or the preset value (based on program code P116).
The message display shows AUTO A(B) and moving arrows to indicate the foam concentrate pump RPM.
With a TankVision Pro connected and program set for tank status (codes P314,P315) the message display
shows the foam type and time remaining at current ow rates A XX.Xm.
Note: The program allows the end user to set the range and the specic increments that are used to
control foam percentage concentration with the + and buttons.
The PRESET or the + and buttons are used to adjust the amount of concentrate (changing the percent)
injected into the discharge water ow to create the foam solution. Both of these functions are programmable to
meet the operators requirements.
If a monitored function is not within normal parameters the FLOW display shows an error or fault warning code
and a description shows in the message display. (Refer to Table 5. Error Codes or Table 6. Fault Warning Codes.)
The remote on/off switch and indicator option duplicate the ON/OFF button and LED. The optional ush
on/off switch and indicator controls the optional ush valve.
Detailed Information
TFC100
The TFC100 does not have a message display. Information is shown in a 4-digit display and on four LEDs.
Operations are the same as TFC200/300/400, substitute MODE button for MENU button in procedure steps.
The TFC100 control module four LEDs indicate the display mode for the 4-digit display; %FOAM, TOTAL
FOAM, FLOW, and TOTAL WATER. Press and release the MODE button to toggle through the display modes.
Foam and water totals are reset to 0 when power goes off. When TOTAL FOAM or TOTAL WATER is shown
on the display, press and hold the MODE button to reset total to 0.
TFC200/300/400
The MENU button allows the operator to gain access to detailed information and some programming features.
Press the MENU button to scroll detailed information and return to normal display.
The total water or total foam values can be reset to zero (0) when shown in the display by holding the MENU
button until the number 0 ashes in the display.
The message display reverts to normal operation after ten (10) seconds if no button is pressed.
Message Display Description
T WATER
* Shows total amount of water ow (in gallons or liters)
T FOAM
* Shows total amount of foam concentrate ow (in gallons or liters)
WATER FLOW Shows water ow rate for each discharge; active only with summing box installed, use the + and buttons to scroll
TANK A
Shows foam concentrate left in tank A; active only with TankVision Pro Foam A installed
TANK B
Shows foam concentrate left in tank B; active only with TankVision Pro Foam B installed
FAULT CODES Shows stored faults with date and time; use the + and buttons to scroll
INCIDENT REPORT Shows stored incidents with date and time; use the + and buttons to scroll
Table 4. Detailed Information
*Note: The total water and total foam ow amounts are reset to zero when the system is powered
down. These can be reset during operations if required.