Calibrate Discharge Flow Sensor (Password Code 1111)
Note: Use a calibrated ow meter or Pitot gauge on the discharge under test as a reference.
When owing water, ensure a constant pressure is maintained to obtain a steady ow rate.
For systems with multiple discharge ow sensors, calibrate each sensor separately.
Select a second reference ow rate and ow water for each discharge to verify the calibration. The ow rate
shown on the FLOW display should match the ow rate shown on the reference meter.
Once the system has been calibrated the System Restore function is used when a component is replaced.
(Refer to Programming Section.)
Single Sensor System
1. Enter password code 1111. (Refer to Password Protected Programs Section.)
Result: The message display shows WATER CAL GPM.
2. Press the MENU button.
Result: The FLOW display shows the ow rate with the last digit ashing.
3. Flow water through the discharge.
4. Set the ow rate shown on the FLOW display to match the ow rate shown on the reference meter.
Press the + and – buttons to change the digit.
Press the PRESET button to move the curser to the next digit.
5. Press and hold the MENU button for ve (5) seconds to save and exit.
Result: The message display shows UPDATING SYSTEM. then CAL DONE .
Multi-Sensor System (w/Summing Box)
1. Enter password code 1111. (Refer to Password Protected Programs Section.)
Result: The message display shows MULTIPLE FLOW CAL.
2. Press the MENU button.
Result: The message display shows the ID name and sensor number.
3. Press the + and – buttons to change the ID name and sensor number.
4. Press the MENU button.
Result: The FLOW display shows the ow rate with the last digit ashing.
5. Flow water through the discharge.
6. Set the ow rate shown on the FLOW display to match the ow rate shown on the reference meter.
Press the + and – buttons to change the digit.
Press the PRESET button to move the curser to the next digit.
7. Press and hold the MENU button until display shows CAL IN PROGRESS to save new setting.
8. Return and repeat steps 3 through 7 or:
9. Press PRESET button to save and exit.
Result: The message display shows UPDATING SYSTEM then CAL DONE .