TFC100 Rev180215
21
PROGRAMMING
Programming functions are allowed when the control module is in the off mode. All program functions are
password protected.
The P-code program functions are available to view and change after the password code has been entered.
Scroll through the P-codes. Use the PRESET button to enter the programming mode and select specic values
(number, word, or symbol) to change. The value blinks and the + and – buttons are used to change that value.
Note: To exit programming modes, press and hold the MENU button for ve (5) seconds.
Enter Password for Program Access
Note: The TFC100 does not have a message display. Information is only shown in the 4-digit display,
procedures are the same. (Substitute MODE for MENU button.)
1. Press and hold the + button for 3 seconds. The FLOW display shows four dashes – – – – and the
message display shows ENTER CODES. Release the button.
2. Press the + and – buttons to enter a code. Each time a button is pressed the rst digit changes by 1.
Set the rst digit to the desired number.
3. Press the PRESET button to move the curser to the next digit. Press the + and – buttons to change
the digit.
4. Repeat step 3 and enter the password code.
Result: When a correct password code is entered the FLOW display ashes the program (P) code and
the message display shows the name of the program or a description of the program code.
5. Press the + and – buttons to scroll through the codes.
6. Use the PRESET button to enter the programming mode and select specic values to change, the +
and – are then used to change the value, the MENU button is used to save the changes.
7. Press and hold the MENU button for ve (5) seconds to exit.
Calibration Passwords 1111 and 1112
Provides access to system programming required for calibration procedures.
1111 - Calibrate Discharge Flow Sensor(s)
1112 - Calibrate Foam Pump
Refer to Calibration Section.
Operator Password 1221
Provides access to system programming P100 codes.
1221 - Operator Programs
Refer to Operator P100 Codes.
Restore Programmed Functions Passwords 5122 and 5123
Provides access to upload all system programming and calibration information from one component to another.
5121 - Initiates Synchronization Between Control Module and Foam Pump Control Programs
5122 - Set/Clear Control Module Restore Flag
5123 - Set/Clear Foam Pump Control Restore Flag
Refer to Restore Programmed Functions Section.