TFC100 Rev180215
61
Figure W2. Control Module Wiring
12-Pin Connector/Cable
Pin/Wire Description
1/Red Supply Power
2/Black Ground
3/Red Sensor 5 Volt
4/White Sensor Signal
5/Green Flush Indicator
6/White Flush Switch
7/White FRC Datalink (+)
8/Green FRC Datalink (–)
9/Black Ground
10 Supply Power (* Tank Empty)
11/Green Remote ON/OFF Indicator
12/White Remote ON/OFF Switch
6-Pin Connector/Cable
Pin/Wire Description
1/Green Tank A Empty Sensor
2/Yellow Tank B Empty Sensor
3/White Select A/B Sensor
4 Spare
5 Spare
6 Spare
Control Module
The control module communicates with other components of the system via the 2-wire FRC datalink.
The datalink is also used to communicate with other FRC products such as the TankVision Pro.
*Pin 10 is Tank Empty Sensor (active low) for TFC100 Only
6-Pin Connector Notes:
- The Tank Empty inputs are used with tank oat switches.
- The Select A/B Sensor input is used when the TFC200 is
installed with a manual ABF selector assembly.
TFC100
TFC200/300/400
Pin 1
Pin 1
Vent
USB
Port*
Pin 1
USB
Port*
Vent
*NOTE: If opened, USB access port plug
must be tightened to a torque of 8-10 in-lbs.
Exceeding this torque value can result in
damage to its water seal capability.