EasyManua.ls Logo

FRC Turbofoam TFC100 - Installation Steps; System Identification and Data Input; Switches and Plumbing Components

FRC Turbofoam TFC100
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TFC100 Rev180215
42
Install System Placards
Three placards are provided for mounting on the pump panel. They are made
of a plate with a decal label. One shows the system basic plumbing diagram, one
outlines the basic operating instructions, and one lists the system specications. The
three mounting plates are the same size (4 1/4" by 4 1/4") and use the same mounting
hole pattern. The mounting holes are clearance or tapped for 10-32 screws. It is easy
to use one of the plates as a template.
Install TankVision Pro Datalink
The FRC TankVision Pro is used to provide the tank empty signal and the time remaining for operation
information via the 2-wire FRC datalink. The signal is available on the TankVision Pro display pins 7(+) and
8(–). Refer to Wiring Section.
Refer to the TankVision Pro technical manual document number XE-WLA3PM-R0A, le reference number
WLA300 for more information.
Install Tank Float Switch for Tank Empty Input
A oat switch can be installed to provide the tank empty signal when a TankVision Pro is not installed.
The TurboFoam requires a signal to ground when the tank is empty. (Refer to Wiring Section.)
Install Remote ON/OFF Switch or Flush Switch
The remote on/off switch and ush switch are wired to the control module. Two connections are available,
one for each switch and one for each indicator light. The switch mounting
hole diameter is 1 3/8" and it uses two 10-32 screws to secure the 2 1/2" by
2 1/2" label plate to the panel. (Refer to Wiring Section.)
Install Foam Strainer and Foam Check Valves
The provided strainer must be installed on the input to the foam pump assembly. A foam tank check valve
must be installed to prevent ush water from getting into the foam tank. Refer to Install Plumbing.
Install Miscellaneous Plumbing
All system components are shipped with the plumbing ttings installed. Hose and hose ttings are not
supplied in the kits. Refer to Install Plumbing.
Install Electric Flush Valve
This valve is standard on TFC300 models and is available as an option for the TFC100/200 single tank
systems, refer to Install Plumbing. The valve is controlled by a pushbutton on the TFC300 control module and
a separate mounted switch and indicator for the TFC100/200 option. The valve cable is connected to the foam
pump control, refer to Wiring Section.