TFC100 Rev180215
53
Figure L10. Discharge Check Valve Assembly Dimensions
Install Discharge Check Valve Assembly Option
The discharge check valve assembly includes a waterway check valve and a check valve injector. A second
option is available that includes the ow sensor mount.
Spring Loaded Check Valve 1.5" 2.0" 2.5" 3.0" 4.0"
Victaulic Coupling 1.5" 2.0" 2.5" 3.0" 4.0"
Height A 4 13/16 5 5/16 5 13/16 6 7/16 7 7/16
Height B 5 1/16 5 9/16 6 1/16 6 11/16 7 11/16
Discharge Check
Valve Assembly
Discharge Check
Valve Assembly
w/Flow Sensor
Note: Allow a minimum of 3
inches clearance above the ow
sensor for removal/installation.
A
B
6" 9 1/2"
Spring Loaded
Check Valve
Spring Loaded
Check Valve
Flow
Sensor
Check Valve
Injector
Check Valve
Injector
WATER FLOW
WATER FLOW