TFC100 Rev180215
23
Operator P100 Codes
The TFC100 does not have a message display. Information is only shown in the 4-digit display, procedures
are the same. (Substitute MODE for MENU.)
When scrolling through the P-codes, some may not be displayed. This happens when a specic code is not
available for access because of other programming settings. (Example: If a system is set for a single A foam tank,
program codes for a B foam tank are not displayed.)
Notes:
1 - Codes P108 and P109: For detailed instructions refer to Set Date and Time.
2 - Code P110: This code is only available when a system has multiple discharge ow sensors. If no
ID names are programmed, the system assigns FLOW 1, FLOW 2, FLOW 3, etc., based on each ow
sensor input connection to the summing box(es). For detailed instructions refer to Set Discharge Flow
Sensor ID Names.
3 - Codes P111 and P115: These codes are used to access information that is stored in various system
devices such as the serial number, manufacture date, or hardware and rmware revisions of that component.
They are only available if the device is detected on the FRC datalink.
4 - Code P116: This code sets the % value when the system is powered on or when switching between
A and B foam tanks (TFC200/400). It can be programed to PRESET (the programmed preset value) or
LAST VAL (the last used value set by the operator).
5 - Code P117: With this code is set to AUTO when power is applied the system the control module is
active and the system is in auto mode (operational).
6 - Codes P118 and P119: These codes are used to set the increment steps when the + and buttons are
pressed. For two tank systems values for both foam A and foam B are set. (TFC200/300/400 shows YES
or NO in the message display, the TFC100 uses the % FOAM LED ; on = yes, off = no.) For detailed
instructions refer to Set +/– Increment Value.
7 - Code P120: This code allows the end user to adjust the elapsed time that passes before the -operate
system warning- goes active. It is recommended that the system be operated at least once every 6 weeks
(42 days). If the concentrate pump is not operated within the set time frame, a message OPERATE
FOAMPUMP shows in the display. The elapsed time clock resets after each pump operation.
8 - Code P122: This code is used to clear the L02 service reminder. The concentrate pump oil must be
changed after the rst 50 hours of operation and then every 500 hours. When these time markers are hit,
the L02 code and the message SVC OIL FOAMPUMP shows in the display. When the oil is changed
access code P122 and set it to YES, this clears the service needed message.