TFC100 Rev180215
50
Fitting Sizes: Fittings Provided with System Kit
Hose Sizes: Hoses Provided by Installer
Standard Fittings are NPT (National Pipe Taper)
Use shortest hose runs possible for concentrate hose lines;
Pump input needs 10" minimum of hose for vibration absorption.
Figure L7. TFC100/200/300 Plumbing Single Tank System w/Electric Flush Valve
Standard All Pumps:
1/2" Female
Standard All Pumps:
1/2" Female
Standard All Pumps:
1/2" Male
Standard All Pumps:
3/4" Male
Clear Suction Hose
23" (584mm) Hg Vacuum; 50 PSI (3 bar)
1.6, 2.1 & 2.6 GPM Pumps: 3/4" (19mm) ID
3.5, 5.0, 6.2, 6.5 GPM Pumps: 1" (25.4mm) ID
Pressure Hose
500 PSI (34 bar)*
Standard All Pumps: 1/2" (13mm) ID
Pressure Hose
500 PSI (34 bar)*
Standard All Pumps: 1/2" (13mm) ID
Tee and ttings
provided by installer.
Clear Suction/Pressure Hose
23" (584mm) Hg Vacuum; 500 PSI (34 bar)
1.6, 2.1 & 2.6 GPM Pumps: 3/4" (19mm) ID
3.5, 5.0, 6.2, 6.5 GPM Pumps: 1" (25.4mm) ID
Standard All Pumps:
1/2" Female
1.6, 2.1 and 2.6 GPM Pumps:
3/4" Female
3.5, 5.0, 6.2, 6.5 GPM Pumps:
1" Female
1.6, 2.1 and 2.6 GPM Pumps:
3/4" Male
3.5, 5.0, 6.2, 6.5 GPM Pumps:
1" Male
Tee and ttings
provided by installer.
*NOTE: Except 2.1 GPM
requires 650 PSI (45 bar)
*NOTE: Except 2.1 GPM