30
CALIBRATION
The components of the TurboFoam system are calibrated at the factory, but plumbing systems are unique
and may cause deviations in the factory calibration. It is recommended that the calibration be checked after
system installation.
The foam pump should be calibrated with the type of foam concentrate that is to be used.
When the discharge ow sensor calibration password code is entered the system automatically detects if
there is a summing box on the datalink and uses the multi-sensor procedure.
Replacing Control Module or Foam Pump Control
The control module, foam pump control module have memory that contains a copy of the system calibration.
This redundancy allows for either component to be replaced without re-programming or re-calibrating the system.
If one is replaced the system calibration can be restored from the memory of the other.
Refer to Programming, Restore Programmed Functions Section.
TankVision Pro Indicator
TankVision Pro indicators connected to the TurboFoam system are required to be calibrate.
Refer to the TankVision Pro Manual, FRC document number XE-WLA3PM-R0A, Calibration Section.
Table 8. Calibration Failure Messages
MESSAGE
DISPLAY
DESCRIPTION
NO FLOW
DETECTED
No signal from the discharge ow sensor
ZERO CAL
ERROR
A ow rate was not entered during the discharge ow sensor calibration procedure