TFC100 Rev180215
20
Table 6. Fault Warning Codes
Code TFC200/300/400
Message Display
Description
F01 FOAM A
LOW
A foam concentrate low
F02 FOAM B
LOW
B foam concentrate low
F03 FOAM A
EMPTY
A foam concentrate tank empty; control module to off mode
F04 FOAM B
EMPTY
B foam concentrate tank empty; control module to off mode
F05 SYSTEM
AT MAX
Request exceeds foam concentrate pump capacity
F01-F04: When tank oat switches are used the codes P309 and P310 set the time delay between the tank
low fault warning (F01, F02) and the tank empty fault warning (F03, F04). When a TankVision Pro is
connected the tank low/tank empty information is provided over the datalink. The concentrate pump is
switched off when the tank empty goes active.
Preset Settings
The preset button allows the operator to go to a pre-programmed percent setting during operations.
The preset value shows in the % display.
Note: The preset setting (selected when the PRESET button is pressed) can only be set to a program
enabled value. Refer to Programming Section for information on Set +/– Increment Value, codes
P118 and P119.
To access the preset setting program the discharge ow must be 0 (FLOW display shows 000).
1. Select A foam tank or B foam tank.
For dual tank systems. TFC200 set the manual ABF selector; TFC400 press the A/B button.
For single tank systems this is set with program code P312.
2. Press and hold PRESET button. (Continue to hold through step 4.)
Result: % display ashes the programmed setting.
3. Press the + and buttons to change setting.
4. Release PRESET button.
Result: The new preset value is programmed.