66
Figure W9. Remote Switch Wiring
REMOTE SWITCH CABLE
4-Wires
Wire Description
Red Supply Voltage
* Green Indicator
* White Switch
Black Ground
Remote ON/OFF Switch or Flush Switch (Option)
The remote on/off switch and ush switch are wired to the control module. Two connections are available,
one for each switch and one for each indicator light.
Remote ON/OFF Switch and Indicator (Option)
The remote switch and indicator mirrors the control module ON/OFF button and LED on the control module.
Flush Switch and Indicator (Option)
The ush switch is provided with the electric ush valve option for TFC100/200 models. The ush switch
also provides prime capabilities if needed for the concentrate pump. (Code P313 set to yes.)
Red
Green
White
Black
(2) Butt-Crimps
Connectors
(2) Deutsch Sockets
10' Cable
* To Control Module 12-Pin Connector
Pin 5 - Flush Indicator
Pin 6 - Flush Switch
Pin 11 - Remote ON/OFF Indicator
Pin 12 - Remote ON/OFF Switch