TFC100 Rev180215
65
Figure W8. Summing Box Wiring
CONNECTOR J2
12-Pin Connector/Cable
Pin/Wire Description
1/Red Sensor +5 VDC
2/Black Sensor Ground
3/White Sensor 3 Signal
4/Red Sensor +5 VDC
5/Black Sensor Ground
6/White Sensor 4 Signal
7/Red Sensor +5 VDC
8/Black Sensor Ground
9/White Sensor 5 Signal
10/Red Sensor +5 VDC
11/Black Sensor Ground
12/White Sensor 6 Signal
CONNECTOR J1
12-Pin Connector/Cable
Pin/Wire Description
1/Red * Supply Power
2/Black* Supply Ground
3/Green* FRC Datalink (–)
4/White* FRC Datalink (+)
5/Black FRC Datalink (–)
6/Red FRC Datalink (+)
7/Red Sensor +5 VDC
8/Black Sensor Ground
9/White Sensor 1 Signal
10/Red Sensor +5 VDC
11/Black Sensor Ground
12/White Sensor 2 Signal
Summing Box (Multiple Flow Sensors Only)
The summing box has two 12-Pin connectors. Each box has inputs
for six (6) discharge ow sensors. Multiple boxes are interconnected using
the FRC datalink. Power is provided by the control model.
CONNECTOR J1
CONNECTOR J2
Summing Box
Top View
Pin 1
*Four conductor cable
from control module.
Note: When more than one box is installed the address
of each box must be set. Refer to Installation Section.
Flow Sensor
Systems with a single discharge ow sensor: The sensor cable is connected directly to the control module.
Systems with multiple ow sensors: The sensor cables are connected to a summing box. The summing box
is connected to the control module via a supply power and FRC datalink cable.
Figure W7. Flow Sensor Wiring
SENSOR CABLE
3-Pin Connector
Pin/Wire Description
A/Black Ground
B/Red Supply Voltage
C/White Signal
Sensor Cable
Signal
Output
Supply
Voltage
Ground
Flow Sensor
Top View
Note: If FRC owmeters (DFA or FPA) are used to retrieve ow rate
information, only the FRC Datalink is connected to the foam system.
IMPORTANT the owmeter ID numbers must be different than the
ow sensor ID numbers used with a summing box.