TFC100 Rev180215
27
Set +/– Increment Value
P118 and P119 codes are available dependent on the setting of code P312. For single tank foam A systems
code P118 is programmable, for a single tank foam B code P119 is programmable. For two tank systems both
P118 and P119 are programmable.
The following percent values are available:
0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1.0, 2.0, 3.0, 4.0, 5.0, 6.0, 7.0, 8.0, 9.0, 10
Example: A system is programmed with code P312 to SINGLE B. This is a foam B system only
where a 1, 3, or 6% mixture is used. Code P119 is set with 1.0, 3.0, and 6.0 YES to enable these
three values, all the rest of the values are set to NO. When the operator presses PRESET or the
+ and buttons only the 1.0, 3.0, and 6.0 foam percents are available.
Notes:
These codes allow the end user to set the range and the specic increments that can be used to control
foam percentage concentration.
The software requires that at least one value is set to YES.
The preset and last used value can only be one of the set values. (The software checks that the current preset
and the last used value matches a set value. If not, the software changes it to the lowest value set at yes.)
The TFC100 does not have a message display. Information is only shown in the 4-digit display, procedures
are the same. (Substitute MODE for MENU.)
Set +/– Increment (Code P118 or P119)
Note: TFC200/300/400 shows YES or NO in the message display, the TFC100 uses the % FOAM
LED ; on = yes, off = no.
Enter password code 1221. (Refer to Enter Password for Program Access.)
1. Press the + and buttons and scroll to code P118 or P119.
2. Press the PRESET button.
Result: The message display shows the % value.
3. Press the PRESET button to select YES or NO.
4 Press the + and buttons to scroll to the next value. Repeat steps 3 and 4 to set all values.
5 Press and hold the MENU button for ve (5) seconds to save.