Operation Notes
If a tank empty signal goes active the foam pump stops. The pump can be run in override mode by pressing the
ON/OFF button. The warning stays active, the pump should not be run with no foam concentrate owing.
If the foam pump motor RPM sensor information is lost the system operates using a pre-programmed plot based
on the current draw of the motor.
If the ow sensor information is lost the system is operated in the manual mode. Refer to Manual Mode.
To complete ushing the system press the ON/OFF button. (If the FLUSH button is pressed, the system re-starts
auto mode.)
Switching Foam Tanks - Automatic Flush (TFC400 Only)
When the control module is in the auto mode the system performs an automatic ush sequence when switching
between the A foam tank and B foam tank. Discharge water must be owing to cycle through the ush mode.
When switching from A foam tank to B foam tank the A/B button is pressed:
The message display shows A - - - > B and status information, the A tank valve closes then the ush valve
opens, the system ushes for the amount of time set in the programming (default is 8 seconds), the ush
valve closes then the B tank valve opens.
When switching from B foam tank to A foam tank the A/B button is pressed:
The message display shows B - - - > A and status information, the B tank valve closes then the ush valve
opens, the system ushes for the amount of time set in the programming (default is 8 seconds), the ush
valve closes then the A tank valve opens.
Manual Mode
The manual mode is used when ow rate information is not received by the control module. It allows the
operator to manually enter a discharge ow rate for system operations. In the manual mode the foam percent value can
be changed by pressing the MENU button and using the + and buttons.
Ensure water continuously ows through the discharge during Manual Mode operation.
The manual mode is activated when discharge water is owing but no ow is indicated in the FLOW display.
Note: Ensure there is foam concentrate in the tank, in manual mode there is no auto shut down of the foam
pump if the tank goes empty.
1. Press both the +/– buttons at the same time for 3 seconds to enter manual mode.
Results: MANUAL MODE ashes in the message display for 3 seconds, the message display changes to show
USE +/– FOR FLOW, the FLOW display and red LED ashes. (TFC100 ashes the ON/OFF LED, the
FLOW LED is on.)
2. Press the MENU button and then press PRESET or +/– buttons to adjust the FLOW or FOAM rates.
Results: The FLOW display shows the operator entered ow rate, the system responds to this data and injects the
correct concentrate into the discharge.
3. Press the MENU button to toggle between setting the flow rate and foam percent value.
Press the PRESET button.
Results: The message display changes to show USE +/– FOR %, the FOAM % display ashes.
(TFC100 the % FOAM LED is on.)
Press the + and buttons to set the %.
Press the MENU button to return to ow rate control.
4. Press the ON/OFF button, the LED goes off; this will stop/start the concentrate pump and shuts down the
TurboFoam system. Press the ON/OFF button again, the LEDs comes on, the system powers on in the
manual mode.
5. Press both the +/– buttons at the same time for 3 seconds to exit manual mode.
NOTE: For the TFC100, substitute MODE button for MENU button in the procedure steps.