QUANTUM
HD COMPRESSOR CONTROL PANEL
MAINTENANCE
090.040-M (NOV 2016)
Page 51
The setpoints can be saved either Locally (default) to the
ashcard on the processor or to a USB Thumb Drive that is
inserted into the USB port of the Quantum HD processor.
Select the [Save Location] button to choose the location to
which the setpoints will be saved.
The same thumb drive that is being used for the program
update can be used to save the setpoints of the controller
prior to doing the update. It is recommended that all locally
saved setpoints be backed up to a USB thumb drive and
stored in a safe, secure location.
Once all of this done simply press the Save button to save
the setpoints to the selected location.
If the setpoints are saved Locally the le name, date and time
will be listed on the left side of the screen as shown below.
Once the setpoints are saved, the Operating Software can
be updated. With the USB thumb drive with the update is
plugged into the USB port of the processor board, select the
Upgrade Software button.
Once after the Upgrade Software button is pushed the screen
will display HD Loading and then the Install page appears as
shown below
To do the install touch the Full System Install button. To abort
the upgrade, touch the Exit button.
Once the update is nished the Please Wait message will
appear and then Operation Complete. Touch the OK button,
then the Exit button.
Once the Exit button is touched you will be prompted “Are
You Sure”. Touch the button for the appropriate response.
When exiting the HD Loading screen will appear briey. After
several seconds, the Quantum HD home screen will reload.
It will be necessary to Login to the service level to restore
the saved setpoints and calibration data.
Once logged in, go to Menu, select Service then select the
Software tab as before. Once on the software page select
Restore Setpoints.
Once restore setpoints is selected the available les will be
displayed what is on the ash card (locally saved) and/or
on the USB device (Thumb Drive) as seen below. Use the
keypad to select the associated number for the setpoints
and calibration data le you wish to restore and touch OK.
You will be prompted to Restore Calibration Data. If the
setpoints were saved from this compressor press Yes, if the
setpoints le was saved form another compressor press No.
Pressing No means that the Calibration Data will be defaulted
and will need to be redone.
Once the setpoints are restored the below screen will appear.
Press Exit to nish this process. Press Yes that you wish to
exit. The HD Loading… screen will appear briey. In several
seconds the Quantum HD home screen will reload. The Op-
erating Software Upgrade and Setpoints Restore is complete.
090.040-PH0017.tif