9. SAFETY DEVICES
Safety device AOU36RLAVM AOU48RLAVM AOU60RLAVM
Fuse
(Filter PCB)
AC 250V 5A
Protector
(Filter PCB)
AC 500V 45A
Compressor
Protector
Overcurrent
protection
-
Temperature
protection
Activate 230°F (110°C): Compressor stop
Reset 176°F (80°C): Compressor restart
High Pressure
Protection
Activate 580 psi (4.0MPa)
Reset 464 psi (3.2 Mpa)
Low Pressure
Protection
Activate 7.25 psi (0.05MPa)
- (03 - 15) -