EasyManua.ls Logo

Fujitsu Airstage J-II Series - Mini Duct Type

Fujitsu Airstage J-II Series
978 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TC : Total Capacity kBtu/h.
SHC : Sensible Heat Capacity kBtu/h.
COOLING CAPACITY
in kBtu/h
Outdoor
temperature
Indoor temperature
68°FDB / 59 °FWB 73°FDB / 61 °FWB 75°FDB / 63 °FWB 79°FDB / 64 °FWB 80°FDB / 67 °FWB 82°FDB / 68 °FWB 86°FDB / 72 °FWB 9FDB / 73 °FWB
FDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
50
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 4.0 2.9 4.2 3.0 4.9 3 .1 5.1 3.5
59
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 4.0 2.9 4.2 3.0 4.9 3 .1 5.1 3.5
70
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 4.0 2.9 4.2 3.0 4.9 3 .1 5.1 3.5
73
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 4.0 2.9 4.2 3.0 4.9 3 .1 5.1 3.5
77
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 4.0 2.9 4.2 3.0 4.9 3 .1 5.0 3.5
81
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 4.0 2.9 4.2 3.0 4.9 3 .1 4.9 3.4
86
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 4.0 2.9 4.2 3.0 4.8 3 .1 4.8 3.4
91
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 4.0 2.9 4.2 3.0 4.7 3.0 4.7 3.3
95
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 4.0 2.9 4.2 3.0 4.6 3.0 4.6 3.3
99
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 4.0 2.9 4.2 3.0 4.5 3.0 4.5 3.3
104
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 4.0 2.9 4.2 3.0 4.4 2.9 4.4 3.2
109
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 4.0 2.9 4.1 3.0 4.3 2.9 4.3 3.2
115
2.5 2.0 2.9 2.5 3.3 2.6 3.5 3.0 3.9 2.8 4.0 2.9 4.2 2.9 4.2 3.2
7- 4. MINI DUCT TYPE
MODEL : ARUL4TLAV1
- (02 - 35) -
MODEL
SELECTION
MODEL
SELECTION

Table of Contents