1-5. WIRING SYSTEM
● Wiring configulation of the control system is made of power source wiring, transmission wiring and remote controller wiring.
● Total wiring length (total length of transmission line) can be extended up to 11,811 ft. (3,600 m) (by using signal amplifiers).
Card key
L
ON
W
ORKS
®
To outdoor units USB Adaptor
NW1
USB
Adaptor
Network Convertor
UTY-VGGX Z1
Network Convertor UTY-VLGX
Network Convertor
UTY-VTGX or UTY-VGGXZ1
Signal Amplier
UTY-VSGX Z1
Web Monitoring Tool
UTY-AMGXZ1
Web Monitoring Tool
Trouble free operation at all times
by remote monitoring system.
Transmission Line
line is non-polar 2-conductor.
Service Tool
Extensive monitoring and analysis
functions for installation and maintenance.
2 Remote Controllers
Indoor unit can be controlled
from both remote controllers.
External Switch Controller
Indoor units can be controlled by combining
with Card-key switch such as hotel room.
System without Remote Controller
Together with Touch panel controller, it is
possible to build non remote controller system.
Remote controller line (3 wire)
Maximum 16 units can be controlled
Touch Panel Controller
One Touch panel controller can control
up to 400 groups / 400 indoor units.
IR Receiver Kit
Cassette type indoor unit can be
controlled with wireless remote controller
IR Receiver Unit
Duct type indoor unit
can be controlled
with wireless remote
controller.
Service Tool
UTY-ASGX Z1
Single system
(VRF network system side)
(Monitoring side)
(Monitoring side)
BACnet
®
Gateway
UTY-ABGX Z1
BACnet
®
L
ON
W
ORKS
®
Network
BACnet
®
11,811 ft.
(3,600 m)
Max. Transmission
line length
BACnet
®
Operator
Workstation (B-OWS)
NW2
NW3
NW4
Combination of individual remote controller
Wired, simple and wireless remote controllers can be used jointly.
(Monitoring side)
Internet
or
Public Telephone Line
USB
Adaptor
USB Adaptor
Internet
or
Public Telephone Line
Internet
Central Remote Controller
Maximum 100 indoor units can be controlled
Remote controller line (2 wire)
Maximum 16 units can be controlled
Indoor unit
(Cassette)
Indoor unit
(Duct)
RB unit
(Single)
RB unit
(Multi)
Touch Panel
Controller
Wired Remote
Controller
Wired Remote
Controller
Central Remote
Controller
Transmission line
Module link
Remote controller
line (3 line)
Remote controller
line (2 line)
Signal line
(single system)
USB cable
System Controller UTY-APGXZ1 or System Controller Lite UTY-ALGXZ1
• Maximum 1,600 indoor units can be controlled. *1
• Air conditioning control
• Operation monitoring
• Status monitoring system
• Electricity charge calculation *2
Case of UTY-ALGXZ1
*1: Maximum 400 indoor units can be controlled.
*2: Option is necessary.
*3: Cannot be used.
(Remote / Monitoring side) *2
(Remote / Monitoring side)
Modbus Convertor UTY-VMGX
Modbus
Network
Modbus
Simple Remote
Controller
Simple Remote
Controller
Simple Remote
Controller
Wireless Remote
Controller
External Switch
Controller
IR Receiver unit
- (05 - 11) -
CONTROL
SYSTEM
CONTROL