1-6. CONTROL EQUIPMENT DESIGN LIMITATION
Model
Necessary
equipment
Connectable
number per
system
Manageable
indoor unit
number
Connectable
outdoor unit
number
Controller
Central
Controller
System Controller
UTY-APGXZ1
UTY-APGX
USB Adaptor 1 / system
1,600
(4 VRF Networks)
400
(4 VRF Networks)
System Controller Lite
UTY-ALGXZ1
UTY-ALGX
USB Adaptor 1 / system
400
(1 VRF Network)
100
(1 VRF Network)
Touch Panel Controller
UTY-DTGYZ1
UTY-DTGY
16 / system
400
100
Central Remote Controller
UTY-DCGY
100
Adaptor / Convertor
Network Convertor
UTY-VTGX
UTY-VGGXZ1
100 / system
*
1
Network Convertor for
L
ON
W
ORKS
®
*
3
UTY-VLGX
1 / system 128 *
2
100
BACnet
®
Gateway
UTY-ABGXZ1
UTY-ABGX
USB Adaptor 1 / system
1,600
(4 VRF Network)
400
(4 VRF Network)
UTY-VBGX
4 / system 128 *
2
100
Modbus
®
Convertor
UTY-VMGX
9 / system 128 *
2
100
Thermostat Convertor UTY-TTRX
16 *
4
Signal Amplier
UTY-VSGX
8 / system
Service and
Maintenance
Service Tool
UTY-ASGXZ1
UTY-ASGX
USB Adaptor
1 / system
400 100
Web Monitoring Tool
UTY-AMGXZ1
UTY-AMGX
USB Adaptor
1,600
(4 VRF Network)
400
(4 VRF Network)
*
1
: Maximum 100 Refrigerant system.
*
2
: Maximum connectable indoor unit number per one Network Convertor.
(Check the System Diagram (Item:3-2) for proper conguration)
*
3
: A maximum of 4 Network Convertors for L
ON
W
ORKS
®
can be connected to 1 BMS.
*
4
: Maximum connectable indoor unit number per one remote controller group.
Model The number that can be connected
Controller
Individual
Controller
Wireless Remote Controller UTY-LNHU
Wired Remote Controller
(Touch panel)
UTY-RNRUZ2
UTY-RNRUZ1
UTY-RNRU
4 / Remote control group
Simple Remote Controller
(with operation mode)
UTY-RSRY
Simple Remote Controller
(without operation mode)
UTY-RHRY
Wired Remote Controller UTY-RNKU
2 / Remote control group
Simple Remote Controller
(with operation mode)
UTY-RSKU
Simple Remote Controller
(without operation mode)
UTY-RHKU
Adaptor / Convertor
External Switch Controller
UTY-TERX
UTY-TEKX
IR Receiver unit 1 / Indoor unit
- (05 - 12) -
CONTROL
SYSTEM
CONTROL
SYSTEM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage J-II Series and is the answer not in the manual?

Fujitsu Airstage J-II Series Specifications

General IconGeneral
BrandFujitsu
ModelAirstage J-II Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals