Model name ARUH72TLAV1 ARUH96TLAV
Power source 1 Phase ~ 208/230V 60Hz
Available voltage range 187 to 253 V
Capacity
Cooling
Btu/h 72,000 96,000
kW 21.1 28.1
Heating
Btu/h 81,000 108,000
kW 23.7 31.7
Input power W 618 838
Static pressure range in.WG(Pa) 0 to 1.2 (0 to 300)
Standard static pressure in.WG(Pa) 0.60(150)
Fan
Airow
rate
High
CFM
(m
3
/ h)
2,296
(3,900)
2,855
(4,850)
Med
1,942
(3,300)
2,502
(4,250)
Low
1,766
(3,000)
2,119
(3,600)
Type x Quantity Sirocco x 2
Motor output W 700 x 2
Sound pressure
level
High
dB(A)
47 48
Med 43 45
Low 40 42
Heat exchanger
Length in. (mm) 49-3/16(1,250)
Fin pitch FPI 17 16
Rows x Stages 4 x 18 4 x 20
Face Area ft
2
. (m
2
) 5.0 (0.47) 6.9 (0.64)
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material)
Slit
(Aluminum)
Louver
(Aluminum)
Surface
treatment
Hydrophilic coating
Air lter (Option)
Model name
- Type
Net material
Enclosure
Material Galvanized sheet iron
Color -
Dimensions
(H x W x D)
Net
in. (mm)
17-11/16 x 62-1/2 x 27-9/16
(450 x 1,587 x 700)
21-5/8 x 62-1/2 x 27-9/16
(550 x 1,587 x 700)
Gross
20-1/2 x 68-7/8 x 32-1/2
(520 x 1,750 x 825)
24-7/16 x 68-7/8 x 32-1/2
(620 x 1,750 x 825)
Weight
Net
lbs. (kg)
203 (92) 231 (105)
Gross 238 (108) 276 (125)
Connection
pipe diameter
Liquid
(Brazing)
in. (mm)
ø1/2 (12.70)
Gas
(Brazing)
ø7/8 (22.22)
Drain hose ø3/4 (19.05) [I.D.]; ø1-1/16 (26.6) [O.D.]
Note : Specications are based on the following conditions.
Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB.
Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB.
Pipe length : 25ft.(7.5 m), Height difference : 0ft.(0 m) (Outdoor unit - Indoor unit).
The protective function might work when using it outside the operation range.
- (04-11) -
INDOOR
UNITS
INDOOR
UNITS

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage J-II Series and is the answer not in the manual?

Fujitsu Airstage J-II Series Specifications

General IconGeneral
BrandFujitsu
ModelAirstage J-II Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals