MCA : Min Circuit Amps = Max Operating Current (Full Load).
MAX.CKT.BKR : Maximum Circuit Breaker.
FLA : Full Load Amps.
2. ELECTRIC CHARACTERISTICS
Indoor Unit Power Supply Indoor Rated
Type Model
Voltage
(V)
Frequency
(Hz)
MCA
(A)
MAX.CKT.
BKR
(A)
Input
Power
(kW)
Current
(A)
FLA
(A)
Compact cassette
AUUA4TLAV1
230 60
0.29
15
0.023 0.17 0.23
AUUA7TLAV 0.51 0.025 0.17
0.41
AUUA9TLAV 0.51 0.025 0.17
0.41
AUUA12TLAV 0.51 0.029 0.20
0.41
AUUA14TLAV 0.51 0.035 0.24
0.41
AUUA18TLAV 0.51 0.036 0.25
0.41
AUUA24TLAV 0.78 0.084 0.62
0.62
Circular ow cassette
AUUB18TLAV1
230
60
0.33
15
0.020 0.20 0.26
AUUB24TLAV1
0.40 0.025 0.24 0.32
AUUB30TLAV1
0.68 0.049 0.41 0.54
AUUB36TLAV1
0.78 0.061 0.47 0.62
AUUB48TLAV1
1.40 0.116 0.86 1.12
Cassette (slim type)
AUUB18TLAV
230 60
0.43
15
0.039 0.27
0.34
AUUB24TLAV 0.43 0.046 0.32
0.34
Cassette
AUUB30TLAV
230 60
0.68
15
0.059 0.42
0.54
AUUB36TLAV 0.68 0.080 0.53
0.54
Mini duct ARUL4TLAV1
230
60
0.35
15
0.026 0.21 0.28
Slim duct /
Slim concealed oor
ARUL7TLAV
230 60
0.71
15
0.044 0.31
0.57
ARUL9TLAV 0.71 0.050 0.35
0.57
ARU L12 TL AV 0.71 0.054 0.38
0.57
ARU L14TL AV 0.76 0.092 0.61
0.61
ARUL18TLAV 0.76 0.083 0.55
0.61
Medium static
Pressure duct
ARUM24TLAV
230 60
1.10
15
0.125 0.75 0.88
ARUM30TLAV
1.40 0.190 1.12 1.12
ARUM36TLAV
1.74 0.222 1.29 1.39
High static
Pressure duct
ARUH36TLAV
230 60
2.70
15
0.496 2.16
2.16
ARUH48TLAV 4.83 0.752 3.27
3.86
ARUH60TLAV 4.83 0.806 3.57
3.86
ARUH72TLAV1
8.13 0.62 3.61 6.50
ARUH96TLAV
9.40 0.84 4.89 7.52
Vertical air handler
ARUV12TLAV
230
60
1.75
15
0.087 0.79 1.40
ARUV18TLAV
2.14 0.142 1.22 1.71
ARUV24TLAV
2.81 0.233 1.77 2.25
ARUV30TLAV
3.38 0.253 1.85 2.70
ARUV36TLAV
4.45 0.427 3.05 3.56
ARUV48TLAV
5.24 0.479 3.28 4.19
ARUV60TLAV
6.98 0.785 5.34 5.58
- (04-22) -
INDOOR
UNITS
INDOOR
UNITS