Model and type Fuse
Fan motor thermal
protector
Terminal
thermal fuse
Float
switch
High static pressure
duct
ARUH36TLAV
250V 3.15A
250V 10A *
1
Activate at
293 ± 9°F
(145 ± 5°C):
Fan motor stop
ARUH48TLAV
ARUH60TLAV
ARUH72TLAV1
250V 3.15A
250V 20A *
1
Activate at
212
+27
-18
°F
(100
+15
-10
°C):
Fan motor stop
Reset at
203
+27
-18
°F
(95+
15
-10
°C)
Fan motor restart
ARUH96TLAV
Vertical air handler
ARUV12TLAV
250V 3.15A
250V 10A *
1
ARUV18TLAV
ARUV24TLAV
ARUV30TLAV
ARUV36TLAV
ARUV48TLAV
ARUV60TLAV
Compact oor
AGUA4TLAV1
250V
3.15A
Activate at
302±27°F
(150±15°C):
Fan motor stop
Reset at
248±27°F
(120±15°C):
Fan motor restart
AGUA7TLAV1
AGUA9TLAV1
AGUA12TL AV1
AGUA14TLAV1
Floor / ceiling
ABUA12TL AV
250V
3.15A
Activate at
275±27°F
(135±15°C):
Fan motor stop
Reset at
239±27°F
(115±15°C):
Fan motor restart
ABUA14TLAV
ABUA18TL AV
ABUA24TLAV
Ceiling
ABUA30TLAV
250V
5A
Activate at
275±27°F
(135±15°C):
Fan motor stop
Reset at
239±27°F
(115±15°C):
Fan motor restart
*
2
ABUA36TLAV
*
1
: Fuse for fan motor.
*
2
: Including in the Drain Pump Unit (Optional parts)
- (04-226) -
INDOOR
UNITS
INDOOR
UNITS

Table of Contents