EasyManua.ls Logo

Fujitsu Airstage J-II Series - Page 359

Fujitsu Airstage J-II Series
978 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Model and type Fuse
Fan motor thermal
protector
Terminal
thermal fuse
Float
switch
High static pressure
duct
ARUH36TLAV
250V 3.15A
250V 10A *
1
Activate at
293 ± 9°F
(145 ± 5°C):
Fan motor stop
ARUH48TLAV
ARUH60TLAV
ARUH72TLAV1
250V 3.15A
250V 20A *
1
Activate at
212
+27
-18
°F
(100
+15
-10
°C):
Fan motor stop
Reset at
203
+27
-18
°F
(95+
15
-10
°C)
Fan motor restart
ARUH96TLAV
Vertical air handler
ARUV12TLAV
250V 3.15A
250V 10A *
1
ARUV18TLAV
ARUV24TLAV
ARUV30TLAV
ARUV36TLAV
ARUV48TLAV
ARUV60TLAV
Compact oor
AGUA4TLAV1
250V
3.15A
Activate at
302±27°F
(150±15°C):
Fan motor stop
Reset at
248±27°F
(120±15°C):
Fan motor restart
AGUA7TLAV1
AGUA9TLAV1
AGUA12TL AV1
AGUA14TLAV1
Floor / ceiling
ABUA12TL AV
250V
3.15A
Activate at
275±27°F
(135±15°C):
Fan motor stop
Reset at
239±27°F
(115±15°C):
Fan motor restart
ABUA14TLAV
ABUA18TL AV
ABUA24TLAV
Ceiling
ABUA30TLAV
250V
5A
Activate at
275±27°F
(135±15°C):
Fan motor stop
Reset at
239±27°F
(115±15°C):
Fan motor restart
*
2
ABUA36TLAV
*
1
: Fuse for fan motor.
*
2
: Including in the Drain Pump Unit (Optional parts)