To protect the compressor of the outdoor unit, the following precautions must be followed prior to setting the
system.
When making changes to system settings, such as the schedule, it is necessary to change the settings
of all indoor units on the same refrigerant circuit at the same time.
<Corresponding function>
More than 10 minutes must elapse
More than 10 minutes must elapse
· Stop operation
· Set indoor unit forced thermostat
o mode
· Start operation
· Release indoor unit forced
thermostat o mode
Forced thermostat OFF instruction
Only one BMS adapter can send this instruction to the refrigerant circuit. If this instruction is sent by more than one
BMS adapter, the system will malfunction.