1-2. VRF NETWORK SYSTEM
MAXIMUM WIRING LENGTH OF VRF NETWORK SYSTEM
Transmission line
Maximum wiring length
ft. (m)
Total wiring length of transmission 11,811 (3,6 0 0)
Maximum wiring length between units 1,312 (400)
Total wiring length in 1 segment * 1,640 (500)
VRF network system segment *
Wiring length [ft (m)] 11,811 (3,60 0) 1,640 (500)
Number of unit 400 64
¾
Segment: Refer to
MAXIMUM CONNECTION OF NETWORK SEGMENT for network
segment gure and explanation.
THE MAXIMUM CONNECTABLE UNIT
z
Outdoor unit and indoor unit
Maximum connectable units in
one VRF network system
Outdoor unit 100
Indoor unit 400
- (06 - 04) -