EasyManua.ls Logo

Fujitsu Airstage J-II Series - Page 579

Fujitsu Airstage J-II Series
978 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CAUTION
Keep the "piping limitation" for correct operation.
z
Allowable height di󰀨erence:
If the height di󰀨erence between the indoor unit and outdoor unit is larger than the allowable value:
¾
The pressure loss will be larger → Insu󰀩cient cooling and heating
¾
The refrigerant in liquid pipe will ush → Refrigerant ow noise generate at indoor unit
¾
The refrigerant oil will not return → Insu󰀩cient refrigerant oil resulting in compressor damage
If the height di󰀨erence between indoor unit is larger than the allowable value:
¾
The refrigerant ow balance will be poor → Insu󰀩cient cooling and heating (poor balance)
¾
Refrigerant oil will collect in the piping or non-operating indoor units
→ Insu󰀩cient refrigerant oil resulting in compressor damage
z
Pipe length:
If the pipe length is longer than prescribed:
¾
The pressure loss will be larger → Insu󰀩cient cooling and heating
¾
Too much refrigerant will be charged → Liquid backs up resulting in compressor damage
¾
The refrigerant oil will not return → Insu󰀩cient refrigerant oil resulting in compressor damage
z
Pipe size:
If the pipe size is larger than designated size:
¾
The refrigerant ow velocity will drop. Refrigerant oil will not return to the outdoor unit.
→ Insu󰀩cient refrigerant oil resulting in compressor damage
¾
The refrigerant in liquid pipe will ush easily → Insu󰀩cient cooling and heating
If the pipe size is smaller than designated size:
¾
The refrigerant circulation volume will drop → Insu󰀩cient cooling and heating
¾
The pressure loss will be larger → Insu󰀩cient cooling and heating
z
Indoor unit connected capacity:
If the indoor unit connected capacity is larger than the system capable capacity:
¾
Insu󰀩cient system performance → Insu󰀩cient cooling and heating
¾
When heating, refrigerant will collect in non-operating indoor units resulting in an insu󰀩cient
refrigerant circulation volume → Insu󰀩cient cooling and heating
¾
The refrigerant oil will not return → Compressor damage
If the indoor unit connected capacity is too small compared to the system capacity:
¾
The liquid return will be too great → Compressor damage
¾
The refrigerant will concentrate in the operating unit
→ Continuous operation will become di󰀩cult due to triggering of the protection in response
to the pressure high-rise, etc., and noise will be generated by the refrigerant ow when heating
- (06 - 15) -
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Related product manuals