WIRING SYSTEM OUTLINE
Remote controller cable (2 line) non-polar 2 core cable,
seathed cable 22-16AWG (0.33-1.25m)m
2
)*Shilded cable
might be required in accordance with the regional standard
Outdoor unit power supply cable
1ø 60 Hz 208 / 230 V
Transmission cable
Non polar 2core,
shielded Level4,
22AWG (0.33 mm
2
)
USB adaptor
(locally
purchased)
USB
adaptor
USB
adaptor
USB
adaptor
Central
Remote
Controller
UTY-ABGX Z1
Network
convertor
for
L
ON
W
ORKS
®
UTY-VLGX
Network convertor
UTY-VGGXZ1
Signal Amplier
UTY-VSGX Z1
Web Monitoring Tool
Internet
or
Public Telephone Line
Transmission line
line is non-polar 2-conductor.
Required in case of follows
Transmission line 1,640 ft. (500 m) or more
Number of unit 64 or more
Can be connect anywhere
on transmission line
(Locally purchased)
(Locally purchased)
External switch controller cable
Polar 3 core, shielded, 22AWG 0.33 mm
2
)
Max length 82 ft. (25 m)
Remote controller cable
Polar 3 core, 22AWG 0.33 mm
2
)
System without remote controller
Together with Touch panel controller, it is
possible to build non remote controller system.
Touch Panel
Controller
IR Receiver Kit
Cassette type indoor unit can be
controlled with wireless remote controller
IR receiver unit
Duct type indoor unit
can be controlled with
wireless remote controller.
Service Tool
Card key
Single system
Outdoor unit
Indoor unit
(Cassette)
Indoor unit
(Duct)
System
Controller
Touch Panel
Controller
Group Remote
Controller
Wired Remote
Controller
Wired Remote
Controller
Simple Remote
Controller
Central Remote
Controller
Simple Remote
Controller
Simple Remote
Controller
Transmission line
Module link
Remote controller
line
Signal line
(single system)
USB cable
Ethernet
L
ON
W
ORKS
®
Network
Wireless Remote
Controller
External Switch
Controller
IR Receiver unit
(VRF system side)
(Monitoring side)
(Monitoring side)
(Monitoring side)
BACnet
®
Gateway
BACnet
®
L
ON
W
ORKS
®
L
ON
W
ORKS
®
Network
BACnet
®
BACnet
®
Operator
Workstation (B-OWS)
NW1
NW2 *2
NW3 *2
NW4 *2
1ø 60 Hz 230 V
1ø 50/60 Hz 220-240 V
1ø 50/60 Hz 220-240 V
1ø 50/60 Hz 100 to 240 V
1ø 50/60 Hz 100 to 240 V
1ø 60 Hz 230 V
1ø 60 Hz 230 V
Indoor unit power supply cable
60Hz 230V ~
1ø 50/60 Hz 220-240 V
1ø 50/60 Hz 220-240 V
Disconnect switch might be required in accordance with the regional standard.
(Remote /
Monitoring
side) *1
(Remote /
Monitoring
side) *1
Remote controller line (3 wire)
Maximum 16 units can be controlled
Total wiring length : Max 1,640 ft. (500 m)
Remote controller line (2 wire)
Maximum 16 units can be controlled
Total wiring length : Max 1,640 ft. (500 m)
Case of UTY-ALGX
*1: Option is necessary.
*2: Can not be used.
- (06 - 38) -
SYSTEM
DESIGN