EasyManua.ls Logo

Fujitsu Airstage J-II Series - Page 604

Fujitsu Airstage J-II Series
978 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
z
Meaning of "Units"
Model name "Units" Count
Indoor unit
(Except Vertical air handler type)
AUUA4TLAV1
AUUA7-24TLAV
AUUB18-48TLAV1
AUUB18-36TLAV
ARUL4TLAV1
ARUL7-18TLAV
ARUM24-36TLAV
ARUH36-60TLAV
AGUA4-14TLAV1
ABUA12-36TLAV
ASUA4-14TLAV1
ASUB18-36TLAV1
ASUA7-14TLAV
ASUB18-24TLAV
1
Indoor unit
(Vertical air handler type)
ARUV12-60TLAV 4
Example 1)
Connectable indoor unit : ASUA9TLAV x 4 + AUUB18TLAV x 2 + ARUL9TLAV
Amount of "Units" : 1 x 4 + 1 x 2 + 1 x 1 = 7
Example 2)
Connectable indoor unit : ARUV12TLAV + AUUA9TLAV x 2 + ARUL9TLAV x 2
Amount of "Units": 4 x 1 + 1 x 2 + 1 x 2 = 8
Select the power cable type and size in accordance with local regulations.
Include at least one breaker and one disconnect per refrigerant system.
Power supply circuits should only be connected to units on the same refrigerant circuit.
Design the power supply circuit to keep the voltage drop within 2%.
- (06 - 40) -
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Related product manuals