TRANSMISSION LINE SEPARATION RULES
●
The transmission line between indoor unit, outdoor unit and controllers can be connected by
one cable.
●
Terminal board available on the market or the ones inside the indoor unit or outdoor should
be used for transmission line separation.
●
Connection of three or more lines may cause poor communication for one terminal. In this
case, use a terminal box.
Note
● Do not loop.
Example 1 : Connecting each outdoor and indoor unit with one connection wiring.
Refrigerant
system 1
Refrigerant
system 2
Refrigerant
system 3
Signal
Amplier
Example 2 : Separating transmission line.
Refrigerant
system 1
Separate on
the terminal for
transmission line.
Separate using
terminal board
System
controller
Refrigerant
system 2
Refrigerant
system 3
- (06 - 47) -
SYSTEM
DESIGN
SYSTEM