SLIM DUCT / SLIM CONCEALED FLOOR TYPE
z
Ceiling concealed setting
Drain hose
Arrange the drain hose
lower than this position
Drain cap
Supporter
Prohibited
Trap
Rise
Air vent
Locally purchased
Max.
11 in.
(300 mm)
ø3/4 [I.D.] ;
ø1-1/16 [O.D.]
Pipe
Supporters
27 in.
(700 mm) or less
Horizontal or
upward slope
Gap of 60 to 79 in. (1.5-2.0 m)
Prohibited
Air vent
Rise
Trap
z
Floor standing concealed setting
Prohibited
Trap
Drain cap
Rise
● Install the drain pipe with downward slope (1/50 to1/100) and so there are no rises or traps in the pipe.
● Use general hard polyvinyl chloride pipe (ø3/4 [I.D.] ; ø1-1/16 [O.D.]) and connect it with adhesive (polyvinyl
chloride) so that there is no leakage.
● Install pipe supports on long lines.
● Do not install air vents on the drain lines.
● Always insulate the drain pipe to prevent condensation.
60 to 79 in.(1.5 to 2.0 m)
- (06 - 56) -
SYSTEM
DESIGN