KINDS OF ADDRESS AND SETTING RANGE
UNIT SETTING
SETTING
RANGE
TYPE OF SWITCH REMARKS
RB unit
O
Refrigerant
circuit address
00 ~ 99
n
Manual address setting
Setting
example
01
Arbitrary numbers can be
set in range of 00-99.
See the setting method 2-9.
n
Automatic address setting
Set this switch to 00 at factory setting.
See the setting method 1-5-3.
P RB unit address 00 ~ 63
n
Manual address setting
Setting
example
12
Arbitrary numbers can be
set in range of 00-63.
See the setting method 2-9
n
Automatic address setting
Set this switch to 00 at factory setting.
See the setting method 1-5-3.
Touch panel
controller
G
Controller /
Convertor
address
00 ~ 15
*1
See the setting method 2-14.
Network
convertor
H
Setting
example
01
See the setting method 2-16.
Refrigerant
circuit address
00 ~ 99
Wired remote
controller
I
Dual remote
control
ON/OFF SW 2 of DIP Switch 1 See the setting method 2-10.
Simple remote
controller
I
Dual remote
control
ON/OFF SW 2 of DIP Switch 1
See the setting method 2-11.
and 2-15.
Signal
amplier
K
Signal amplier
address
1 ~ 8
n
Manual address setting
See the setting method 2-17.
n
Automatic address setting
Set to 1 at factory setting.
See the setting method 1-5-1
Modbus
®
convertor
Q
Controller /
Convertor
address
00 ~ 15
*1
See the setting method 2-18.
Network
co nver tor for
L
ON
W
ORKS
®
M See the setting method 2-19.
Central
remote
controller
N See the setting method 2-13.
Wired remote
controller
(Touch panel)
F
Remote
controller
address
1 ~ 32
*2
n
Manual address setting
See the setting method 2-14-1.
0 ~ 15
n
Automatic address setting
J
Dual remote
control
ON/OFF See the setting method 2-14-2.
*Set up after conrming the details of each unit.
*1: The sum total of the Touch panel controller, Central remote controller and Network convertor for L
ON
W
ORKS
®
is a
maximum of 16.
NOTE:
Address of the Touch panel controller, Central remote controller, Modbus
®
convertor and Network convertor
for LONWORKS® must not be same.
*2: The address can be set from 1 to 32. However, do not set the same number as that for the remote-controller
address of an indoor unit connected using the same remote-control cable.
Set "Remote controller address" of Wired remote controller (Touch panel) in Manual address setting only. It is not
necessary to set in Automatic address setting.
REF AD
x10
REF AD
x1
RB AD
x10
RB AD
x1
SW 110 SW 111
(10 digit) (1 digit)
- (07 - 04) -
FUNCTION
SETTING
FUNCTION
SETTING

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage J-II Series and is the answer not in the manual?

Fujitsu Airstage J-II Series Specifications

General IconGeneral
BrandFujitsu
ModelAirstage J-II Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals