COMPENSATION COEFFICIENT OF FROSTING / DEFROSTING
(HEATING OPER ATION)
To take the eects of accumulated frost and defrosting operation on heating capacity into
consideration, the capacity of outdoor unit should be corrected by compensation coecient
shown in the table below.
Outdoor temperature
°FDB /
°FWB
5 / 3 16 / 14 19 / 18 23 / 21 27 / 25 32 / 30 36 / 34 41 / 39 45 / 43
°CDB /
°CWB
-15 / -16 -9 / -10 -7 / -8 -5 / -6 -3 / -4 0 / -1 2 / 1 5 / 4 7 / 6
Compensation coecient % 0.96 0.94 0.91 0.88 0.85 0.83 0.85 0.90 1.00