Example 2 : To automatically set the addresses of signal ampliers only
(When the addresses of indoor units and RB units will be set
manually)
Follow the step below
3
2
1
Refrigerant system1
Refrigerant system2
Refrigerant system3
Master unit
Heat Recovery system
Heat Recovery system
Heat Pump system
Step 1:
Activate the Signal Amplier Automatic Address Setting function on the master
unit of Refrigerant System 1.
An address is automatically assigned to all signal ampliers on the network.
CAUTION
● When indoor units are being connected via different refrigerant systems, never activate the Indoor
Unit Automatic Address Setting function.
● As long as master units are on the same network, any master unit can set the addresses of signal
amplifiers automatically.Perform the automatic address setting of signal amplifiers on only one
outdoor unit (master unit) within the same network. (Do not set them again from other outdoor
unit.)
- (07 - 54) -