LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Outdoor unit
Remarks
Master Slave
3 0
Energy saving
level setting
0 0 Level 1 (stop)
l
¡
-
*1
The capacity limit can be
selected by the external
input terminal (CN133) when
operating with the “Energy
Saving Peak Cut function.
The lower the level, the more
the e󰀨ect of energy saving, but
the cooling/heating performance
will also drop.
0 1
Level 2 (operated at
40% capacity)
0 2
Level 3 (operated at
60% capacity)
0 3
Level 4 (operated at
80% capacity)
0 4
Level 5 (operated at
100% capacity)
3 2 Prohibited
0 0 Prohibited
l
Setting prohibited0 1 Prohibited
0 2 Prohibited
3 3 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
3 5
Presence of
heater selection
control using
outdoor
temperature
0 0 Disable
l
¡
-
*1
Setting required to validate
the setting of heater selection
control using outdoor
temperature 1 and 2 (setting
value: 03 or 04) in eld setting
61 (indoor unit) for heater
control switching.
For details, refer to Chapter 8.
1-2-2. EXTERNAL OUTPUT.
0 1 Enable
3 6
Outdoor
temperature
zone boundary
temperature
A
0 0 -4.0°F (-20°C)
l
¡
-
*1
Setting required if changing
of the outdoor temperature
setting for heat pump prohibition
zone is required when heater
selection control using outdoor
temperature 1 and 2 are
performed on the indoor unit.
For details, refer to Chapter 8.
1-2-2. EXTERNAL OUTPUT.
0 1 -0.4°F (-18°C)
0 2 3.2°F (-16°C)
0 3 6.8°F (-14°C)
0 4 10.F (-12°C)
0 5 14.0°F (-10°C)
0 6 17.6°F (-8°C)
0 7 21.2°F (-6°C)
0 8 24.8°F (-4°C)
3 7
Outdoor
temperature
zone boundary
temperature
B
0 0 42.8°F (6°C)
l
¡
-
*1
Setting required if changing
of the outdoor temperature
setting for heat pump only
zone is required when heater
selection control using outdoor
temperature 1 is performed on
the indoor unit.
For details, refer to Chapter 8.
1-2-2. EXTERNAL OUTPUT.
0 1 14.0°F (-10°C)
0 2 17.6°F (-8°C)
0 3 21.2°F (-6°C)
0 4 24.8°F (-4°C)
0 5 28.4°F (-2°C)
0 6 32.0°F (0°C)
0 7 35.6°F (2°C)
0 8 39.2°F (4°C)
0 9 42.8°F (6°C)
1 0 46.4°F (8°C)
1 1 50.0°F (10°C)
1 2 53.6°F (12°C)
1 3 57.2°F (14°C)
1 4 60.8°F (16°C)
1 5 64.4°F (18°C)
*1: Do not set this for outdoor units with Slave setting.
- (07 - 63) -
FUNCTION
SETTING
FUNCTION
SETTING