EasyManua.ls Logo

Fujitsu Airstage J-II Series - Page 712

Fujitsu Airstage J-II Series
978 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Outdoor unit
Remarks
Master Slave
7 0
Electricity meter
No. setting 1
*2
0 0 Setting number x00
l
¡ ¡
Set the ones digit and tens digit
of the No. of the electricity meter
connected to CN135.
0 1 Setting number x01
9 8 Setting number x98
9 9 Setting number x99
7 1
Electricity meter
No. setting 2
*2"
0 0 Setting number 0xx
l
¡ ¡
Set the hundreds digit of the
No. of the electricity meter
connected to CN135.
0 1 Setting number 1xx
0 2 Setting number 2xx
7 2
Electricity meter
pulse setting 1
*3"
0 0 Setting number xx00
l
¡ ¡
Set the ones digit and tens
digit of the No. of the electricity
meter pulse setting connected
to CN135.
0 1 Setting number xx01
9 8 Setting number xx98
9 9 Setting number xx99
7 3
Electricity meter
pulse setting 2
*3"
0 0 Setting number 00xx
l
¡ ¡
Set the hundreds digit and
thousands digit of the electricity
meter pulse setting connected
to CN135.
0 1 Setting number 01xx
9 8 Setting number 98xx
9 9 Setting number 99xx
*2: When electricity meter No. is set to “000” and “201 to 299”, the pulses input to CN135 become ine󰀨ective.
Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to “0000, the pulses input to CN135 become ine󰀨ective.
Available setting number is "0001" to "9999"
- (07 - 65) -
FUNCTION
SETTING
FUNCTION
SETTING

Table of Contents

Related product manuals