LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Remarks
7 0
Electricity meter
No. setting 1
*1
0 0 Setting number x00
l
Set the ones digit and tens digit of the No. of
the electricity meter connected to CN135.
0 1 Setting number x01
9 8 Setting number x98
9 9 Setting number x99
7 1
Electricity meter
No. setting 2
*1
0 0 Setting number 0xx
l
Set the hundreds digit of the No. of the
electricity meter connected to CN135.
0 1 Setting number 1xx
0 2 Setting number 2xx
7 2
Electricity meter
pulse setting 1
*2
0 0 Setting number xx00
l
Set the ones digit and tens digit of the No. of
the electricity meter pulse setting connected to
CN135.
0 1 Setting number xx01
9 8 Setting number xx98
9 9 Setting number xx99
7 3
Electricity meter
pulse setting 2
*2
0 0 Setting number 00xx
l
Set the hundreds digit and thousands digit of
the electricity meter pulse setting connected to
CN135.
0 1 Setting number 01xx
9 8 Setting number 98xx
9 9 Setting number 99xx
9 0 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
0 2 Prohibited
0 3 Prohibited
0 4 Prohibited
0 5 Prohibited
0 6 Prohibited
0 7 Prohibited
0 8 Prohibited
0 9 Prohibited
1 0 Prohibited
1 1 Prohibited
*1: When electricity meter No. is set to “000” and “201 to 299, the pulses input to CN135 become ine󰀨ective.
Available setting number is "001" to "200"
*2: When the electricity meter pulse setting is set to “0000, the pulses input to CN135 become ine󰀨ective.
Available setting number is "0001" to "9999"