1-1-4. OUTDOOR UNIT EXTERNAL INPUT / OUTPUT
FUNCTION SUMMARY
OUTDOOR UNIT EXTERNAL INPUT FUNCTION
Item
Dry contact /
Apply voltage
Function Specications
Emergency
stop
Low noise
mode
operation
Cooling/
Heating
priority
Outdoor
unit
operation
peak
control
Batch stop
Power
usage
information
from
electricity
meter
Terminal
Signal
type
Outdoor unit
input function
specication
Dry contact
DC12[V]
-
*2 - - - -
CN 131
(PIN 1-2)
Edge
- -
- - -
CN 132
(PIN 1-2)
- - -
*1 - -
CN 133
(PIN 1-2)
(20 -01) - - -
(20-00) -
CN 134
(PIN 1-2)
- - - - - -
CN 135
(PIN 1-2)
Pulse
*1 : If you use Outdoor unit operation peak control, select energy saving level from below.
30-00 Energy saving level 1 (Stop)
30-01 Energy saving level 2 (Operated at 40% capacity)
30-02 Energy saving level 3 (Operated at 60% capacity)
30-03 Energy saving level 4 (Operated at 80% capacity)
30-03 Energy saving level 5 (Operated at 100% capacity)
*2 : If you use Low noise mode operation, select low noise level from below.
42-00 Low noise level 1 (lower than rated value)
42-01 Low noise level 2 (lower than level 1)
NOTES :
For selecting relay, minimum permissible load must be less than 1 (mA).
When you use Apply voltage, Take "+" polarity for PIN 1
Number inside bracket "()" indicates function number and setting number.
Expression "
" is equipping function.
OUTDOOR UNIT EXTERNAL OUTPUT FUNCTION
Item
Dry contact /
Apply voltage
Function Specications
Operation
status
Error
status
Base
heater
Terminal
Terminal
output
voltage
External power supply
Allowable
voltage
Allowable
current
Outdoor unit
output function
specication
Apply voltage
-
- CN 136 (PIN 1-2)
-
DC12-24
[V]
30 mA or
less
- - CN 137 (PIN 1-2)
Dry contact - -
CN 115 (PIN 1-3) AC240 [V] - 1 A or less
NOTES :
When you use Apply voltage, Take "+" porarity for PIN 1
Expression "" is equipping function.
- (08 - 07) -
EXTERNAL INPUT
& OUTPUT
EXTERNAL INPUT
& OUTPUT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage J-II Series and is the answer not in the manual?

Fujitsu Airstage J-II Series Specifications

General IconGeneral
BrandFujitsu
ModelAirstage J-II Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals