AUXILIARY HEATER CONTROL 1
Operation Condition
Heater ON Heater ON as shown in diagram of heating temperature
Heater OFF
Heater OFF as shown in diagram of heating temperature
Other than Heating mode
Error occurred
Forced thermostat off
Fan stop protection
Temperature of heater ON (Thon) ... Adjustable by Function setting No.62 (Operating
temperature switching of external heaters).
All control temperatures will shift by adjusting "Thon".
OFF
OFF
ON
Tr-Ts ≥ -1.8°F
(-1°C)
Tr-Ts
Tr-Ts (=Thon) < -5.4°F
(
-C)
Tr-Ts ≥ -18°F
(-10°C
Tr-Ts < -21.6°F (-12°C)
A
Tr: Room temperature
Ts: Set temperature
Thon: Heater ON temperature
Example. When Set Temperature (Ts) is 72°F (22°C) *Factory setting
and Room Temperature (Tr) increase above 53.6°F
(
12°C), signal output is on.
and Room Temperature (Tr) increase above 69.8°F (21°C), signal output is off.
and Room Temperature (Tr) decrease below 66.2°F (19°C), signal output is on.
▪and Room Temperature (Tr) decrease below 50°F (10°C), signal output is off.
AUXILIARY HEATER CONTROL 2
Control that excludes "A" from Auxiliary heater control 1 mentioned above.
Operation Condition
Heater ON Heater ON as shown in diagram of heating temperature
Heater OFF
Heater OFF as shown in diagram of heating temperature
Other than Heating mode
Error occurred
Forced thermostat off
Fan stop protection
Temperature of heater ON (Thon) ... Adjustable by Function setting No.62 (Operating
temperature switching of external heaters).
All control temperatures will shift by adjusting "Thon".
Tr: Room temperature
Ts: Set temperature
Thon: Heater ON temperature
OFF
ON
Tr-Ts ≥ -1.8°F
(-1°C)
Tr-Ts
Tr-Ts (=Thon) < -5.4°F
(
-C)
- (08 - 35) -
EXTERNAL INPUT
& OUTPUT
EXTERNAL INPUT
& OUTPUT