Operation status
ON
ON
ON
12 V
OFF
OFF
OFF
0 V
Heater
Fan
DIP-SW2-3 ON
DIP-SW2-3 OFF
EEV ON/OFF
Outdoor temperature
(Factory setting)
Outdoor temperature zone *
Heat pump
prohibition
zone
Combination zone
* The Outdoor temperature zone transition from one to another will stay in that zone for
minimum 30 min.
46.F (8°C)
42.F (6°C)
-0.4°F (-18°C)
-4°F (-20°C)
NOTES :
In following operations, EEV will be ON in Heat pump prohibition zone.
- Other than Heating
- Test Run
This control is enable when the setting code no. 35 of the outdoor unit (Presence of heater
selection control by outdoor temperature) is "Enable".
- (08 - 41) -
EXTERNAL INPUT
& OUTPUT
EXTERNAL INPUT
& OUTPUT