Chapter 2: Front panel programming
36 Vigilant VS1 and VS2 Technical Reference Manual
Default passwords
The panel comes standard with a set of default passwords. These are:
Level 1: 1111
Level 2: 2222
Remote annunciator: 3333
Note: It is recommended that you change the default passwords before
programming the system.
Default panel operation settings
• Language: English
• Marketplace: US
AC fail delay: 3 hours
Zone resound: On
• Reset inhibit: Off
Auto signal silence: Off
Suite signal silence: 10 minutes
Day start: 06:00
Night start: 18:00
Date format U.S.: MM/DD/YYYY
Aux power reset: On
LCD banner: Blank
Event notification: Device
Key #1: Disabled
Key #2: Disabled
Other default panel settings
• Daylight savings
Enabled: No
Month start: 03
Month end: 11
Week start: 1
Week end: 0
Weekday start: 0
Weekday end: 0
Hour start: 02
Hour end: 02
Offset minutes: 60
RS232 CU Enable: Off
Lock remote read: No
Default panel configuration settings
• IP: 192.168.001.003
Subnet mask: 255.255.255.0
• Gateway: 000.000.000.000
• Panel NACs
Class: Class B
Type: Genesis - audible visible silence
Correlation group: 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS1 and is the answer not in the manual?

GE Security Vigilant VS1 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS1
CategoryControl Panel
LanguageEnglish

Related product manuals