Appendix B -Settings and Signals
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
Setting of ZP residual compensation angle.
kZmP Mut. Comp. 32 87 1
From 0 to 10 in steps of 0.01
Setting of ZP mutual compensation magnitude.
kZmP Mut. Angle 32 88 0
From -180 to 90 in steps of 0.1
[Courier Number (angle)]
Setting of ZP mutual compensation angle.
RP Gnd Resistive 32 89 20
From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1
[Courier Number (impedance)]
Setting for ZP ground resistive reach.
ZP Sensit Ignd>P 32 8B 0.05
From 0.05*I1 to 2*I1 in steps of 0.005*I1
[Courier Number (current)]
Zone P current sensitivity.
Z4 Gnd. Reach 32 90 15
From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1
[Courier Number (impedance)]
Setting for Z4 reach. This is a common setting for Z4 time delayed and Z4 high speed elements used in blocking schemes and for current
reversal guard.
Z4 Gnd. Angle 32 91 70
From 20 to 90 in steps of 1
[Courier Number (angle)]
Setting of line angle (positive sequence) for zone 4.
Z4 Dynamic Tilt 32 93 Enabled
Enabled
Setting that enables or disables Z4 top reactance line dynamic tilting. If set enabled, the top line angle will be automatically shifted by the
angle difference between the fault current and negative sequence current, starting from the ‘Z4 Tilt top line’ angle setting – see the next cell.
The Z4, as over-reaching zone, is allowed only to tilt up. If Dynamic tilting is disabled, the top line will be shifted by the ‘Z4 Tilt top line’ setting
(Predetermined tilting by fixed angle).
This setting is visible only when ground characteristic is set to ‘Quad’.
Z4 Tilt Top Line 32 94 -3
From -30 to 30 in steps of 1
[Courier Number (angle)]
Setting of the Z4 tilt angle. Minus angle tilts the reactance line downwards This setting is visible only when the above setting is visible.
kZN4 Res. Comp. 32 95 1
From 0 to 10 in steps of 0.01
[Courier Number]
Setting of Z4 residual compensation magnitude.
kZN4 Res. Angle 32 96 0
From -180 to 90 in steps of 0.1
[Courier Number (angle)]
Setting of Z4 residual compensation angle.
kZm4 Mut. Comp. 32 97 1
From 0 to 10 in steps of 0.01
[Courier Number]
Setting of Z4 mutual compensation magnitude.
kZm4 Mut. Angle 32 98 0
From -180 to 90 in steps of 0.1
[Courier Number (angle)]
Setting of Z4 mutual compensation angle.
R4 Gnd Resistive 32 99 15
From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1
[Courier Number (impedance)]
Setting for Z4 ground resistive reach.
Z4 Sensit Ignd>4 32 9B 0.05
From 0.05*I1 to 2*I1 in steps of 0.005*I1
[Courier Number (current)]
Zone 4 current sensitivity.
34 00
This column contains settings for Distance Scheme Logic
Zone1 Tripping 34 08 Phase And Ground
Phase only
Ground only
Phase And Ground
Setting to select for which types of fault Zone 1 elements will be applied.
From 0 to 10 in steps of 0.01