Appendix B -Settings and Signals
P446SV
B104
P446SV-TM-EN-1
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
[Courier Number (time-seconds)]
Time delay for Z1 phase element.
tZ1 Gnd. Delay 34 0A 0
From 0 to 10 in steps of 0.01
[Courier Number (time-seconds)]
Time delay for Z1 ground element.
Zone2 Tripping 34 10 Phase And Ground
Disabled
Phase only
Ground only
Phase And Ground
[Indexed String]
Setting to select for which types of fault Zone 2 elements will be applied.
tZ2 Ph. Delay 34 11 0.2
From 0 to 10 in steps of 0.01
[Courier Number (time-seconds)]
Time delay for Z2 phase element.
tZ2 Gnd. Delay 34 12 0.2
From 0 to 10 in steps of 0.01
[Courier Number (time-seconds)]
Time delay for Z2 ground element.
Zone3 Tripping 34 18 Phase And Ground
Disabled
Phase only
Ground only
Phase And Ground
[Indexed String]
Setting to select for which types of fault Zone 3 elements will be applied.
tZ3 Ph. Delay 34 19 0.6
From 0 to 10 in steps of 0.01
[Courier Number (time-seconds)]
Time delay for Z3 phase element.
tZ3 Gnd. Delay 34 1A 0.6
From 0 to 10 in steps of 0.01
[Courier Number (time-seconds)]
Time delay for Z3 ground element.
ZoneP Tripping 34 20 Phase And Ground
Disabled
Phase only
Ground only
Phase And Ground
[Indexed String]
Setting to select for which types of fault Zone P elements will be applied.
tZP Ph. Delay 34 21 0.4
From 0 to 10 in steps of 0.01
[Courier Number (time-seconds)]
Time delay for ZP phase element.
tZP Gnd. Delay 34 22 0.4
From 0 to 10 in steps of 0.01
[Courier Number (time-seconds)]
Time delay for ZP ground element.
Zone4 Tripping 34 28 Phase And Ground
Disabled
Phase only
Ground only
Phase And Ground
[Indexed String]
Setting to select for which types of fault Zone 4 elements will be applied.
tZ4 Ph. Delay 34 29 1
From 0 to 10 in steps of 0.01
[Courier Number (time-seconds)]
Time delay for Z4 phase element.
tZ4 Gnd. Delay 34 2A 1
From 0 to 10 in steps of 0.01
[Courier Number (time-seconds)]
Time delay for Z4 ground element.
Aid. 1 Selection 34 41 Disabled
Disabled
PUR
PUR Unblocking
POR
POR Unblocking
Blocking 1
Blocking 2